Fire protection

Fully sprinklered & base building fire alarm systems and risers

Mechanical cooling

7 w/SF of cooling for lab areas
2 w/SF of cooling for office areas

Mechanical Ventilation

1.2 to 1.6 CFM/SF ventilation for lab areas
(6 to 8 ACH)

STRUCTURAL BAYS

33' X 45' (lab/ steel construction)

Vibration Criteria - Lab

VC-A (4,000 mips) with additional reinforcing by tenant agreement for additional as needed vibration control

Plumbing Lab Waste

Provide dedicated pre-plumbed areas for tenants acid neutralization systems and
lab waste

electrical

10 w/SF for lab areas
8 w/SF for office areas

Elevator

One (2) stop 1,500 lb. passenger
One (3) stop 4,500 lb. freight

WIRED SCORE

Certified

Telecom

Fiber ready